Quick answer
Choose a backup battery by checking energy, power and system design together. Available kilowatt-hours (kWh) help determine runtime; output kilowatts (kW) determine how much equipment can operate simultaneously. Starting capability matters for motors, and the installed backup equipment determines which circuits work during an outage. Battery capacity alone cannot answer all three questions. (energylibrary.tesla.com)
Your first step: Write down what must stay powered, for how long, and what can remain off. Ask a qualified installer to assess that list before recommending battery models or quantities.
Scope: U.S. homeowner planning. Manufacturer examples were checked on November 25, 2026; regional specifications are identified where used.
1. Start with essential loads—not your entire electricity bill
Instead of asking, “What battery size does my house need?” ask, “What must this battery keep running?”
Create three groups:
- Must run: Your household’s essential refrigeration, lighting, communications, pumps or heating equipment.
- Can run occasionally: Equipment you could use briefly or schedule around other loads.
- Can stay off: Equipment you agree to exclude during an outage.
These are priorities to discuss, not a universal list. A well pump might be essential at one property and irrelevant at another. NYSERDA advises homeowners to work with their contractor to determine which circuits should receive backup power. (nyserda.ny.gov)
For each item, record:
| Information to collect | Why the installer needs it |
|---|---|
| Appliance model and circuit | Identifies the equipment and proposed backup coverage |
| Running watts or measured consumption | Supports the operating-load estimate |
| Hours of use during the target outage | Supports the energy calculation |
| Motor-start requirements, if applicable | Helps check starting capability |
| Whether it must run alongside other equipment | Helps check simultaneous demand |
Appliance labels are a useful starting point, but actual consumption depends on operating settings and cycling. Refrigerators, for example, do not draw their running power continuously. Motor starting can also demand more current than normal operation. Have a qualified professional assess hardwired equipment and starting loads; do not open electrical panels to gather measurements. (pubs.ext.vt.edu)
2. Read energy capacity and output power separately
Energy capacity, in kWh, describes an amount of stored energy. Power, in kW, describes the rate at which energy is delivered. A 1 kW load operating for one hour consumes 1 kWh. Virginia Cooperative Extension expresses the same relationship as watts multiplied by operating hours, divided by 1,000. (pubs.ext.vt.edu)
Read these specifications separately:
- Usable energy: The manufacturer’s stated accessible capacity, subject to its definitions and conditions.
- Continuous output: The power the system can sustain under the specified conditions.
- Peak or surge output: A temporary output limit that must include a duration.
- Motor-start capability: A separate specification or assessment for starting equipment such as compressors and pumps.
Manufacturer documents show why the distinctions matter. Tesla’s U.S. Powerwall 3 specifications list 13.5 kWh of nominal battery energy alongside AC output configurations of 5.8, 7.6, 10 and 11.5 kW. The same energy figure therefore does not establish the configured output. (energylibrary.tesla.com)
Enphase’s April 2026 Latin America/Caribbean IQ Battery 5P datasheet lists 5.0 kWh usable capacity, 3.84 kVA continuous output at 240 V, and peak-current durations of three and ten seconds. This is a regional illustration—not a substitute for a U.S. proposal’s datasheet. Preserve the manufacturer’s units: if a document uses kVA or starting amperes, ask the designer to explain the applicable limit rather than relabeling it as kW. (enphase.com)
Practical check: Ask for the installed system’s battery-only continuous output during an outage, plus its starting capability—not just the largest power number in an advertisement.
3. Check what “usable” and “backup reserve” actually mean
Do not assume every advertised kWh will reach household appliances during every outage.
Read the capacity footnotes. For example, Enphase’s regional datasheet says its stated usable capacity includes energy maintained for asset protection and battery electronics. That illustrates why a headline capacity needs its accompanying definition. (enphase.com)
Also distinguish a backup reserve setting from a protective shutdown threshold.
Tesla describes Backup Reserve as stored energy held back from normal daily operation for an outage. During an outage, that reserve becomes available, and the battery may discharge below the selected reserve percentage. It is not simply an untouchable block that must always be subtracted from outage capacity. (tesla.com)
Ask the installer:
- What charge level is assumed when the outage begins?
- What capacity definition supports the runtime estimate?
- What energy remains unavailable at protective shutdown?
- Does the estimate include conversion losses and system consumption?
- How would the estimate change under the proposed reserve setting?
For a simple illustration, a hypothetical 10 kWh battery beginning an outage at 60% charge does not begin with 10 kWh available. If charge percentage maps proportionally to that stated capacity, it begins with approximately 6 kWh before applicable deductions. That is planning arithmetic, not a prediction for a particular product.
4. Work through a 12-hour essential-load example
The following figures are invented planning assumptions, not measured appliance consumption or a claim about any household.
Assume a homeowner wants these loads covered for a 12-hour overnight outage:
| Hypothetical load | Assumed use | Energy required |
|---|---|---|
| Refrigerator | 80 W average over 12 hours | 0.96 kWh |
| Internet equipment | 20 W for 12 hours | 0.24 kWh |
| LED lighting | 40 W for 5 hours | 0.20 kWh |
| Phone and laptop charging | Combined allowance | 0.20 kWh |
| Small fan | 40 W for 8 hours | 0.32 kWh |
| Total | 1.92 kWh |
The calculation follows:
Energy = watts × hours ÷ 1,000.
The refrigerator assumption is an average across cycling, not its instantaneous running or starting demand. (pubs.ext.vt.edu)
For arithmetic only, suppose the designer has allowed 4.0 kWh delivered to household circuits after accounting for starting charge, losses, protective limits and system consumption. The 1.92 kWh schedule fits within that hypothetical energy budget, leaving 2.08 kWh. It still needs a separate power and motor-start check.
Now change one assumption: add a hypothetical 1.5 kW electric heater running continuously for four hours.
1.5 kW × 4 hours = 6.0 kWh.
Total demand becomes 7.92 kWh, exceeding the 4.0 kWh budget. A battery might have sufficient output to run the heater but insufficient energy to run it for the requested duration. Tesla likewise identifies electric heating, air conditioning and vehicle charging as energy-intensive uses to limit when extending backup duration. (tesla.com)
Use this example as a worksheet structure. Replace every assumption with your own equipment information and have the installer assess simultaneous loads, starting demand and operating margins.
5. Define selected-load versus whole-home backup
With selected-load or partial-home backup, the design supplies specified essential circuits during an outage. With whole-home backup, the design extends backup coverage across the home. Tesla documents both arrangements and makes system sizing dependent on household demand and battery quantity. (tesla.com)
However, “whole-home” should not replace a written operating plan. Connected appliances still have to remain within the system’s output and energy limits; excessive simultaneous demand can overload a battery system. (tesla.com)
Ask the proposal to state:
- Which circuits receive backup power?
- Which appliances can operate simultaneously?
- Which loads must stay off or be controlled?
- What happens when a pump or compressor starts?
- Does additional storage increase energy, output power, or both?
The battery enclosure is not the complete backup installation. Tesla’s documented designs include a gateway or backup switch, and partial-home layouts can include a separate backup panel. The applicable equipment depends on the system and site. (tesla.com)
Request a written demonstration plan covering outage transfer, intended loads and return to grid operation. Any commissioning or outage simulation should be performed by the qualified installer—not improvised by the homeowner.
6. Treat solar recharging as conditional
Existing solar panels do not automatically mean the house can recharge a battery during an outage.
The Department of Energy explains that grid-dependent residential solar systems generally shut down when grid power fails. Outage operation requires an appropriately configured system capable of operating independently of the grid. (energy.gov)
Even a compatible solar-and-battery installation cannot promise the same recharge every day. Outages associated with severe weather may coincide with lower solar production. Tesla also documents that low-energy recovery requires enough solar to support household demand while recharging the battery. (tesla.com)
For an illustrative balance, suppose an outage-capable system supplies 5 kWh of solar energy during the day while daytime household loads consume 4 kWh. Only 1 kWh remains before applicable charging losses and limits. It would be incorrect to count all 5 kWh as battery recharge.
Request three scenarios:
- Overnight, without solar.
- A low-solar outage day.
- A favorable solar day.
Also ask what happens after the battery reaches its protective shutdown threshold: can the proposed configuration restart from solar, under what conditions, and with which loads connected? Get a model-specific answer rather than assuming all batteries recover identically.

7. Compare proposals using the same backup target
Give every bidder the same load list, outage duration and solar assumptions. Then request these items in writing:
| Proposal item | What a useful answer contains |
|---|---|
| Equipment | Exact battery, inverter and backup-control models |
| Energy | Stated capacity definition and estimated delivered outage energy |
| Output | Battery-only continuous output and time-limited starting capability |
| Coverage | Included circuits, excluded loads and operating restrictions |
| Runtime | Starting charge, load schedule, losses and solar assumptions |
| Installed scope | Backup controls, panel work, permits, commissioning and exclusions |
| Ownership planning | Applicable warranty documents, service process and shutdown/recovery guidance |
Avoid four common mistakes: comparing only kWh, treating surge output as continuous output, assuming every outage starts with a full battery, and counting expected solar production as guaranteed recharge. Manufacturer specifications and operating guidance distinguish these limits for good reason. (energylibrary.tesla.com)
If a bidder promises “a day of backup,” ask them to translate that into named loads, operating hours and explicit assumptions.
The most useful proposal is not necessarily the one with the largest battery. It is the one that clearly shows whether your essential loads fit within both the available energy budget and the installed system’s power limits.